Installation and Servicing Instructions
FAN POWERED HIGH EFFICIENCY
MODULATING DOMESTIC CONDENSING
GAS BOILER
CE/PI No. 86-CL-08
System 30 - GC No. 41-930-39
System 30
These instructions must be left either with the
user or next to the site gas meter.
Keston Heating
PO Box 103, National Avenue, Kingston Upon Hull, HU5 4JN
Tel. +44 (0) 1482 443005 Fax. +44 (0) 1482 467133
email : [email protected] web : www.keston.co.uk
COMPLIANT WITH BUILDING REGULATION PART L1 & L2
SEDBUK A RATED
Vue de la page 0
1 2 3 4 5 6 ... 67 68

Résumé du contenu

Page 1 - System 30

Installation and Servicing InstructionsFAN POWERED HIGH EFFICIENCYMODULATING DOMESTIC CONDENSINGGAS BOILERCE/PI No. 86-CL-08System 30 - GC No. 41-93

Page 2 - Keston System

10 Keston System - Installation and ServicinggeneralModel 30Max CH uutput kW 30.3 (Btu/h) (103,300)Water ow rate l/min 21.5 (gal/min) (4.7)Te

Page 3 - DOCUMENT AMENDMENTS

11Keston System - Installation and Servicinggeneral The boiler does not normally need a bypass but at least some radiators on the heating circuit, of

Page 4

12 Keston System - Installation and ServicinggeneralNote that item numbers are linked to the spares list104 CH RETURN VALVE105 CH FLOW VALVE108 PUM

Page 5 - CONTENTS

13Keston System - Installation and Servicinggeneral 6 UNPACKINGUnpack and check the contents.Pack A ContentsA BoilerB Hardware Pack BoxC Wall Mounti

Page 6

14 INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET8 FLUE SYSTEMWhen installing a replacement boiler a new ue system must be used.

Page 7

15INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET SLOPE‘Horizontal’ ue outlet pipework MUST slope at least 1.5 degrees (26mm per m

Page 8 - IMPORTANT

16 INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET10 FLUE INSTALLATION EXAMPLE KESTON SYSTEM 3011 FLUE INSTALLATION EXAMPLE KESTON

Page 9 - * Bottom clearance

17INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET 12 FLUE TERMINATION POSITIONTwin Flue PositionsBelow an opening (1)Above an openi

Page 10 - Installation and Servicing

18 INSTALLATIONKeston System - Installation and Servicing FLUE OUTLETThe wall mounting template is located on the internal protective packaging.Note.

Page 11 - CENTRAL HEATING

19INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET 3G9948Example of fixing17 MOUNTING THE BOILER1. Ensure the plastic plug is remo

Page 12

2 Keston System - Installation and Servicing

Page 13

20 INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET19 FITTING THE SLEEVINGFlue SleeveFlue PipeFlueTerminalFlexibleWallSeal WallPla

Page 14 - FLUE OUTLET

21INSTALLATIONKeston System - Installation and Servicing 20 CONDENSATE DRAIN20347149CondensateDrainThis appliance is tted with a siphonic 75mm cond

Page 15

22 INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET21 CONDENSATE DRAIN - CONT’D...Visible air breakCondensate pump(Install in a

Page 16

23INSTALLATIONKeston System - Installation and Servicing FLUE OUTLET INSTALLATION22 CONNECTIONS & FILLINGNOTES. Ensure all boss blanking plugs ar

Page 17

24 INSTALLATIONKeston System - Installation and Servicing24 INTERNAL WIRINGThe Keston System boiler comes pre-tted with 1.8m of mains cable. This

Page 18

25INSTALLATIONKeston System - Installation and Servicing 26 REPLACING PRE-FITTED MAINS CABLEIf it is necessary to use an alternative mains cable to t

Page 19

26 INSTALLATIONKeston System - Installation and ServicingFITTING THE KITFitting the sensorThe air sensor should be located on an external wall of the

Page 20

27INSTALLATIONKeston System - Installation and Servicing 28 FITTING THE WEATHER COMPENSATION KIT - SUPPLIED AS STANDARDwgog/ybBOILERLNEsLOUTSIDESENSO

Page 21

28 INSTALLATIONKeston System - Installation and Servicing30 EXTERNAL ELECTRICAL CONTROLSWiring External to the BoilerThe fuse rating should be 3A.Wir

Page 22

29INSTALLATIONKeston System - Installation and Servicing 31 WIRING DIAGRAMsLENLWaterPressureSensorFanReturnThermistorFlowThermistorFlameSensorElectro

Page 23

3Keston System - Installation and Servicing Keston reserve the right to vary specication without noticeRelevant Installation changes implemented in t

Page 24

30 INSTALLATIONKeston System - Installation and ServicingWARNING. Whilst effecting the required gas tightness test and purging air from the gas instal

Page 25

31INSTALLATIONKeston System - Installation and Servicing 33 INITIAL LIGHTINGTHE DISPLAYThe user control has one neon and one display to inform the us

Page 26 - Kit Contents

32 INSTALLATIONKeston System - Installation and Servicing36 HANDING OVER8. Loss of system water pressure Explain that the dial underneath the boil

Page 27

33SERVICINGKeston System - Installation and Servicing 37 SERVICING SCHEDULEFor the very latest copy of literature for specication & maintenance

Page 28 - Heating slope

34 SERVICINGKeston System - Installation and Servicing38 BOILER FRONT PANEL REMOVAL / REPLACEMENTREMOVAL1. Loosen the two screws retaining the front

Page 29

35SERVICINGKeston System - Installation and Servicing 40 BURNER REMOVAL AND CLEANING1. Ensure the sump is fully drained2. Undo the two screws and r

Page 30 - ATTENTION !

36 SERVICINGKeston System - Installation and Servicing342 CLEANING THE HEAT EXCHANGERNote: Ensure the condensate trap/siphon is fully drained before c

Page 31

37SERVICINGKeston System - Installation and Servicing 44 REPLACEMENT OF COMPONENTSGENERAL When replacing ANY component1. Isolate the electricity su

Page 32

38 SERVICINGKeston System - Installation and Servicing43346 BURNER INJECTOR REPLACEMENT1. Refer to Frame 44.2. Disconnect the electrical leads from

Page 33 - 

39SERVICINGKeston System - Installation and Servicing 48 RETURN THERMISTOR RENEWAL1. Refer to Frame 44.2. Unclip the return thermistor from the re

Page 34

4 Keston System - Installation and Servicinggeneral Keston System 30 Gas supply 2H - G20 - 20mbar Gas Supply Connection 15mm c

Page 35

40 SERVICINGKeston System - Installation and Servicing3mmStraight edge50 IGNITION ELECTRODE REPLACEMENT1. Refer to Frame 44.2. Remove the burner.

Page 36

41SERVICINGKeston System - Installation and Servicing 52 SPARK GENERATOR REPLACEMENT1. Refer to Frame 44.2. Disconnect the leads from the spark gen

Page 37

42 SERVICINGKeston System - Installation and Servicing1. Refer to Frame 44.Note: Ensure condensate trap is fully drained before removal. 2. Pull off

Page 38

43SERVICINGKeston System - Installation and Servicing 55 MAIN PCB REPLACEMENTNote. Fit the earth strap provided with the PCB to your wrist and secure

Page 39

44 SERVICINGKeston System - Installation and ServicingNote. Fit the earth strap provided with the PCB to your wrist and a suitable earth on the boiler

Page 40

45SERVICINGKeston System - Installation and Servicing 59 SAFETY RELIEF VALVE RENEWAL1. Refer to Frame 44.2. Drain the boiler. Refer to Frame 57.3.

Page 41

46 SERVICINGKeston System - Installation and Servicing61 PUMP HEAD REPLACEMENT1. Refer to Frame 44.2. Drain the boiler. Refer to Frame 57.3. Disco

Page 42

47SERVICINGKeston System - Installation and Servicing 64 HEAT ENGINE RENEWALRefer also to Frame 5 - ‘Boiler Exploded View’IMPORTANTBefore starting th

Page 43

48 SERVICINGKeston System - Installation and Servicing66 BOILER SEALING PANEL SEAL REPLACEMENT65 EXPANSION VESSEL RECHARGING & REPLACEMENT71.

Page 44

49Fault FindingFault Finding Fault Finding Fault Finding Fault Finding Fault FindingKeston System - Installation and Servicing 67 FAULT FINDING CHAR

Page 45

5Keston System - Installation and Servicinggeneral Boiler size G.C. Appliance No. PI No. (Benchmark No.)30 41-930-39 86 CL 08CONTENTS Benchmark

Page 46

50 Fault FindingFault Finding Fault Finding Fault Finding Fault Finding Fault FindingKeston System - Installation and Servicing68 ALTERNATING ‘L’ AND

Page 47

51Fault FindingFault Finding Fault Finding Fault Finding Fault Finding Fault FindingKeston System - Installation and Servicing 70 ALTERNATING ‘L’ AND

Page 48

52 Fault FindingFault Finding Fault Finding Fault Finding Fault Finding Fault FindingKeston System - Installation and Servicing73 ALTERNATING ‘F’ AND

Page 49

53Fault FindingFault Finding Fault Finding Fault Finding Fault Finding Fault FindingKeston System - Installation and Servicing 76 ALTERNATING ‘F’ AND

Page 50

54 Fault FindingFault Finding Fault Finding Fault Finding Fault Finding Fault FindingKeston System - Installation and Servicing79 NO DISPLAYIs there

Page 51

55Short liSt of partSKeston System - Installation and Servicing When replacing any part on this appliance use only spare parts that you can be assure

Page 53

© Heating and Hotwater Industry Council (HHIC)www.centralheating.co.ukBenchmark Commissioning andServicing Section It is a requirement that the boiler

Page 54

* All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A

Page 55 - Short liSt of partS

* All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A

Page 56

6 Keston System - Installation and ServicinggeneralINTRODUCTIONThe Keston System boiler is wall mounted, full sequence, automatic spark ignition, low

Page 57 - Servicing Section

60 Keston System - Installation and ServicingFLOWCHART FOR CO LEVEL AND COMBUSTION RATIOCHECK ON COMMISSIONING A CONDENSING BOILERImportant Preliminar

Page 58

61Keston System - Installation and Servicing NoNoYesNoNoYesYesYesYesNoIsCO level less than 350ppm AND CO/CO2 ratio less than0.0040?Turn off Appliance

Page 59 - SERVICE RECORD

February 2014 UIN 208893 A04Keston pursues a policy of continuing improvement in the design and performance of its products. The right is there

Page 60

User InstructionsFAN POWERED HIGH EFFICIENCYMODULATING DOMESTIC CONDENSINGGAS BOILERCE/PI No. 86-CL-08System 30 - GC No. 41-930-39System 30These ins

Page 61

2 Keston System - User’sMinimum ClearancesClearances of 165mm (6 1/2”) above, 100mm (4”) below, 2.5mm (1/8”) at the sides and 450mm (17 3/4”) at the f

Page 62

3Keston System - User’s A G BC DLegendA. CH Temperature ControlB. Mode ControlC. Boiler Status1 BOILER CONTROLSNote. The pump will operat

Page 63

4 Keston System - User’sDISPLAY CODE ON BOILERDESCRIPTIONThe boiler is in standby mode awaiting either a central heating call or hot water demand.The

Page 64

5Keston System - User’s Outside Sensor FailureReset the appliance - if the boiler fails to operate then please contact Keston (if under warranty) or a

Page 65 - A G BC D

Keston pursues a policy of continuing improvement in the design and performance of its products. The right is therefore reserved to vary specication

Page 66 - OPERATION MODES

7Keston System - Installation and Servicinggeneral SAFETYCurrent Gas Safety (installation and use) regulations or rules in force: The appliance is sui

Page 67 - FAULT CODES

8 Keston System - Installation and ServicinggeneralGAS SUPPLYThe local gas supplier should be consulted, at the installation planning stage, in order

Page 68

9Keston System - Installation and Servicinggeneral 1 BOILER DIMENSIONS, SERVICES & CLEARANCESall dimensions in mmThe boiler connections are made