Qudos 28h
User, Installation and Servicing
Instructions
FAN POWERED HIGH EFFICIENCY
MODULATING DOMESTIC CONDENSING
GAS HEAT ONLY BOILER
CE/PI No. 86-CM-43
Qudos 28h - GC No. 41-930-19
Qudos 28hP - GC No. 41-930-20
These instructions must be left either with the
user or next to the site gas meter.
Keston Heating
PO Box 103, National Avenue, Kingston Upon Hull, HU5 4JN
Tel. +44 (0) 1482 443005 Fax. +44 (0) 1482 467133
email : info@keston.co.uk web : www.keston.co.uk
COMPLIANT WITH BUILDING REGULATION PART L1 & L2
SEDBUK A RATED
WD 440
issue 7 - 2011
Vue de la page 0
1 2 3 4 5 6 ... 58 59

Résumé du contenu

Page 1 - Qudos 28h

Qudos 28h User, Installation and Servicing Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS HEAT ONLY BOILER CE/PI No.

Page 2 - CONTENTS

function, automatic pump and fan exercise in periods of inactivity, anti cycle control anddry fire protection.2.2 BOILER SCHEMATICAir is drawn into

Page 3 - Page : ii

The flue gases are piped in a 50 mm muPVC (BS5255 and/or and BSEN1329) plastic or,alternatively, 75mm Keston composite plastic pipe to outside. The t

Page 4 - 0. HANDLING INSTRUCTIONS

BS 6891 : Low Pressure Installation PipesBS 6798 : Installation of Gas Fired Hot Water Boilers of Rated Input Not Exceeding 70kWBS 5449 : Installation

Page 5 - Page : iv

2.4 PHYSICAL DATA - Qudos 28h & Qudos 28hPCabinet Height mm 680Cabinet Width mm 390Cabinet Depth mm 280Top Clearance mm 150Side Clearance mm 5Base

Page 6 - 1. USER INSTRUCTIONS

2.6 PERFORMANCE DATA - Qudos 28h & Qudos 28hPSeasonal Efficiency (SEDBUK) = 91.1 (Qudos 28h) & 93.1 (Qudos 28hP)This value is used in the

Page 7

appliance. When replacing these articles we recommend that the replaced items are notbroken up, but are sealed within heavy duty polythene bags,

Page 8

3. BOILER LOCATION3.1 DIMENSIONS AND MINIMUMCLEARANCESThe boiler must be installed in minimumclearances shown to allow subsequentservicing,

Page 9 - 2. GENERAL INSTRUCTION

Compartment installation is permitted - such compartments must be constructed inaccordance with BS 6798.The wall on which the boiler i

Page 10 - ENTER RESET

The appliance must be connected to the 3A supply via a fused double-pole switchhaving at least 3 mm (1/8 inch) contact separation in both poles, servi

Page 11

3.5 BOILER SIZE SELECTIONThe Qudos 28h will automatically adjust heat output to match the system requirements atany given time. Efficiency and co

Page 12

CONTENTSNB : These instructions are an integral part of the appliance. This document must be handed over tothe user on completion of the installation

Page 13

.WD440/3/2007 Chapter 3 - Boiler Location The Keston Qudos 28h & Qudos 28hP BoilersInstallation & Servicing Instructions Page : 15P

Page 14 - (Factory Preset)

h Jointing should be either with capillary, threaded or compression fittings. Pipesshould have a gradient to ensure air is passed e

Page 15

capable of meeting the flow rate required at the total pressure loss generated by the boilerand the rest of the system. The selected pump must comply

Page 16 - 3. BOILER LOCATION

A 92.5o sweep elbow is equivalent to 1.0m straight length. A 45o bend is equivalent to0.5m straight length.50mm 75mmMaximum Air Inlet Length : 39.0m 1

Page 17

The Keston Qudos 28h and Qudos 28hP, as with any condensing boiler, willgenerate a condensate “plume” from the flue terminal in a

Page 18

External wall faces and any internal faces of cavity walls must be made good. Rubbercollars are available for flue and air terminals t

Page 19

4. INSTALLATION OF THE BOILERRead Chapter 3 - Boiler Location and decide upon the position of the boiler.Installation of the boiler is straightforward

Page 20

NB: When installing the boiler, consider:Flue Spigot AssemblyThe flue spigot (50mm muPVC) is inside the accessory bag.Put the flue spigot assembled wi

Page 21 - Q28h hydraulic resistance

4.6 WATER SYSTEMConnect the flow and return HEATING CIRCUIT system pipework to the boiler. Details ofsystem requirements are given in Chapter 3 - Sect

Page 22 - Figure 3.8.1 : Terminals

4.9 Advanced Features WiringThe Qudos 28h features comprehensive and advance functionality as standard.Whilst these advances functions are

Page 23 - 7R%RLOHU

5.7 Combustion Testing5.8 Checking The Gas Pressure5.9 Timing The Gas Meter5.10 Handing Over To The User6 FAULT FINDING6.1 Electrical Control Sequence

Page 24

4.9.3 Solar Control4.10 EXCHANGING A BOILERBefore removing an existing boiler add Fernox Supafloc, or equivalent cleaning agent, inaccordance with t

Page 25

(minimum 18 mbar required for Natural Gas and 31 mbar required for LP gas). If all jointsare sound and the gas inlet pressure is satisfactory set t

Page 26 - 4. INSTALLATION OF THE BOILER

5. COMMISSIONING OF THE BOILERImportant:This condensing boiler contains components which could be damaged or blocked by grease, dirt,solder etc., fr

Page 27

“RESET” button so that the display reverts to show the actual flow temperature ofthe boiler. Once a heating demand is received the fan will start and

Page 28

To measure CO2 levels in the Kestonboiler remove the 1/8" plug from theflue outlet pipe spigot (Figure 6.7.4item 17). Insert

Page 29 - MAIN CONNECTOR

7) Press the “RESET” button twice to return to the normal operation mode anddisplay.5.8 CHECKING THE GAS PRESSUREWith the boiler running

Page 30 - SOLAR PANEL

6. FAULT FINDING6.1 ELECTRICAL CONTROL SEQUENCEWhen the main external control(s) are calling for heat, power will be fed to the boiler

Page 31

QUICK REFERENCE6.2 NORMAL OPERATIONThe Qudos 28h and Qudos 28hP boilers feature a user display which shows actual flowtemperature. Howev

Page 32

6.3 FAULT MODESIf a situation is detected which the boiler considers may cause damage to the appliance the boilerwill enter a lockout mode and stop fu

Page 33

ERROR HISTORYThe Qudos 28h has an internal memory function that stores the last six errorsencountered along with the sensor readings a

Page 34

0. HANDLING INSTRUCTIONS0.1 LIST OF CONTENTSThe Keston Qudos 28h and Qudos 28hP are supplied almost totally pre-assembled. The unitsuse standard 50 mm

Page 35

6.4 FUNCTIONAL FLOW WIRING DIAGRAMWD440/3/2007 Chapter 6 : Fault Finding The Keston Qudos 28h & Qudos 28hP BoilersInstallation & Servicing

Page 36 - 6. FAULT FINDING

6.5 ELECTRICAL WIRING DIAGRAMWD440/3/2007 Chapter 6 : Fault Finding The Keston Qudos 28h & Qudos 28hP BoilersInstallation & Servicing Instruc

Page 37 - QUICK REFERENCE

6.6 ILLUSTRATED WIRING DIAGRAMWD440/3/2007 Chapter 6 : Fault Finding The Keston Qudos 28h & Qudos 28hP BoilersInstallation & Servicing Instr

Page 38 - 6.3 FAULT MODES

6.7 Exploded Assembly Diagrams6.7.1 Boiler Controls Assembly WD440/3/2007 Chapter 6 : Fault Finding The Keston Qudos 28h & Qudos 28hP BoilersInst

Page 39 - ERROR HISTORY

6.7.2 Waterway, Condensate & Flue AssemblyWD440/3/2007 Chapter 6 : Fault Finding The Keston Qudos 28h & Qudos 28hP BoilersInstallation &

Page 40

6.7.3 Air  Gas AssemblyWD440/3/2007 Chapter 6 : Fault Finding The Keston Qudos 28h & Qudos 28hP BoilersInstallation & Servicing Instructions

Page 41 - 6.5 ELECTRICAL WIRING DIAGRAM

6.7.4 Casing AssemblyWD440/3/2007 Chapter 6 : Fault Finding The Keston Qudos 28h & Qudos 28hP BoilersInstallation & Servicing Instructions P

Page 42

6.7.5 Exploded Diagrams Parts Reference ListBoiler Controls Assembly (Fig. 6.7.1)GC Number Code Description111 Q28h Main Control PCB(Q.10S.4.01.00.0

Page 43

7. ROUTINE (ANNUAL) SERVICINGTo ensure the continued safe and efficient operation of the boiler it is necessary to carry outroutine s

Page 44

c. If necessary clean the burner with a mild household detergent and rinse under ahot running tap.d. If necessary, from visual inspection, clean

Page 45 - 6.7.3 Air  Gas Assembly

then tilt the boiler forwards from its back onto its base and remove carton by sliding up overthe boiler. When lifting this appliance the back

Page 46 - 6.7.4 Casing Assembly

8. REPLACEMENT OF PARTSCONTENTS8.0 GENERAL8.1 PRECAUTIONS8.2 ACCESS8.3 REPLACEMENT PROCEDURE8.4 ELECTRICAL COMPONENTS8.4.1 CONTROL PANEL8.4.2 BOILER F

Page 47

8.4.2 Boiler Flow and Return Thermistors (Fig. 6.7.2 item 48)i) Isolate the appliance (Section 8.1)ii) Gain access (Section 8.2)iii) Remove the push o

Page 48 - 7. ROUTINE (ANNUAL) SERVICING

iv) Unscrew the bolts (Fig 6.7.3 item 94) securing the gas inlet pipe to the gascontrol valve.v) Remove the four nuts securing the combustion blower (

Page 49

8.7 HEAT EXCHANGER (Fig. 6.7.2 item 41)i) Isolate the appliance (Section 8.1)ii) Gain access (Section 8.2)iii) Shut off the water supply to the applia

Page 50 - 8. REPLACEMENT OF PARTS

9. SHORT SPARE PARTS LISTItem GC No Part Denomination Item GC No Part Denomination42 Burner KIT 64 Burner Gasket55 Ignitor Gasket 43 Igni

Page 51

163 Q28h Gas Valve - Mixer Assem. 91 FanQ28hP Gas Valve - Mixer Assem.112 Control Panel 111 Q28h Control PCB Q28hP Con. PCBWD440/

Page 52

SHORT SPARE PARTS LIST FOR THE KESTONCONDENSING BOILER RANGEItem GC No Part Denomination42 Burner KIT64 Burner Gasket43 Ignitor KIT55 Ignitor Gasket48

Page 53

WD440/3/2007 Chapter 10 : Benchmark Checklist Final The Keston Qudos 28h & Qudos 28hP Boilers Installation & Servicing Instructio

Page 54 - 9. SHORT SPARE PARTS LIST

WD440/3/2007 Chapter 10 : Benchmark Checklist Final The Keston Qudos 28h & Qudos 28hP Boilers Installation & Servicing Instructio

Page 55

bRead Installation Manual CarefullybEnsure that ALL dust particles, filings , plastic chips etc. areremoved from the inlet pipe.bIf the i

Page 56 - CONDENSING BOILER RANGE

1. USER INSTRUCTIONS1.1 INTRODUCTIONThank you for choosing this Keston Qudos 28h for your household heating. The boiler isdesigned to be

Page 57 - BENCHMARK No

Normal OperationDuring normal operation the digital display will show the current boiler temperature and willshow relevant operational symb

Page 58 - SERVICE INTERVAL RECORD

1.4 SAFETY INFORMATIONIF YOU SUSPECT A GAS LEAK TURN OFF THE APPLIANCE IMMEDIATELY, TURN OFFTHE GAS TAP TO THE APPLIANCE (LOCATED UNDERNEATH) AN

Page 59 - Qudos 28h and Qudos 28hP

2. GENERAL INSTRUCTION2.1 DESCRIPTIONThe KESTON Qudos 28h and Qudos 28hP boilers utilise the latest in condensingtechnology to produce